Definition and Grade Correspondence
TP2 refrigerant tube is seamless copper tube manufactured for refrigerant circuits, air-conditioning systems and heat pumps. The material is phosphorus-deoxidised copper: TP2 in the Chinese grade system and C12200 in the UNS system, with copper plus silver at 99.90 % minimum and phosphorus in the range 0.015–0.040 %. European and American trade literature calls the same product ACR tube, refrigeration tube or air-conditioning tube.
Two characteristics separate refrigerant tube from ordinary plumbing tube. The first is chemistry: the deoxidised grade is used because refrigerant circuits are brazed, and a tough-pitch copper would be at risk of hydrogen embrittlement every time a joint is made. The second is cleanliness. A refrigerant circuit is a sealed system charged with oil and refrigerant, and any moisture, oxide scale or drawing residue left inside the tube can cause acid formation, capillary blockage in expansion devices and premature compressor failure. The product standards therefore control the internal surface as strictly as they control the dimensions.
Chemistry and Product Standards
| Item | Requirement or reference |
|---|---|
| Material | TP2 / C12200 phosphorus-deoxidised copper |
| Copper plus silver | 99.90 % min |
| Phosphorus | 0.015–0.040 % |
| Oxygen | Kept low by deoxidation; no dispersed oxide inclusions |
| Other impurities | Limited to the maximum sum given in the product standard |
| American standard | ASTM B280, seamless copper tube for air conditioning and refrigeration field service |
| Chinese standard | GB/T 17791, copper tube for air conditioners and refrigeration equipment |
| European standards | EN 12735-1 and EN 12735-2 for copper and copper-alloy tubes for air conditioning and refrigeration |
| Non-destructive test | Eddy-current examination to ASTM E243 |
ASTM B280 covers the tube used in field-installed refrigerant piping, while the equipment manufacturers work to their own specifications built on the same chemistry. Size ranges are expressed as outside diameter and wall thickness rather than as nominal bore, because a refrigeration circuit is sized by pressure and by heat transfer rather than by flow area alone.
Mechanical, Physical and Thermal Data
| Property | Typical value | Comment |
|---|---|---|
| Density | 8.94 g/cm³ | At 20 °C |
| Electrical conductivity | 80–85 % IACS | Annealed condition |
| Thermal conductivity | about 340 W/(m·K) | At 20 °C, annealed |
| Tensile strength, soft temper | 220–280 MPa | Typical range for annealed tube |
| Elongation, soft temper | 40 % and above | Enables field bending and flaring |
| Melting range | about 1083 °C | Brazing is carried out well below this |
| Working fluid compatibility | HFC, HFO, HC and CO₂ refrigerants with suitable lubricant | Copper is chemically compatible with the common refrigerants |
Copper is compatible with the refrigerants in normal use, including R32, R410A, R134a, R290 and R744, provided the correct lubricant and a dry, clean circuit are used. The tube itself contributes no reactive elements to the system, and the absence of oxide inclusions removes one of the classic sources of internal contamination. Annealed tube in the soft temper is the standard supply condition because it permits bending around ductwork and pipework in the field without additional joints.
Cleanliness, Pressure and Testing Requirements
The internal surface is the heart of a refrigerant tube specification. Tube is drawn with lubricants, annealed in a controlled atmosphere, then purged, dried and capped. The product standards set a maximum residue limit expressed per unit area of internal surface, and the tube is delivered with the ends sealed so that the cleanliness achieved at the mill survives transport and site storage. Nitrogen purging during brazing is standard practice on the installation side, because it prevents oxide scale from forming on the hot internal surface while joints are made.
Pressure performance is verified by hydrostatic proof testing and by burst testing of finished tube rather than by a single published figure, since the capability of the tube depends on the exact diameter and wall thickness supplied. In practice, thin-wall ACR tube is qualified to withstand internal pressures far above the working pressures encountered in air-conditioning and heat-pump circuits, which for R410A systems are typically around 4 MPa on the high side. Where higher pressures are used, such as transcritical CO₂ systems, the wall thickness is increased and the design is checked against the applicable pressure-equipment code.
Bending, Flaring and Joining
Soft annealed refrigerant tube can be bent by hand bender or by powered bender to a minimum centre-line radius of about one and a half to two times the outside diameter. Flaring for flare-nut connections requires annealed tube and an eccentric-cone flaring tool; flareless compression and press fittings are also used. Where the tube is bent to a tight radius, the wall thins on the outside of the bend and thickens on the inside, so the bend radius permitted by the manufacturer's design guide should be respected.
Brazing with a silver-based filler under a nitrogen purge is the standard jointing method. The joint is made with the tube and fitting at the correct clearance, heated uniformly, and allowed to cool naturally after the filler has flowed; quenching a hot brazed joint in water is poor practice because it can crack the filler or distort the tube. Solder joints are used on some lower-pressure duties, but brazed joints are preferred for refrigeration piping. Before the circuit is charged it is evacuated to the level required by the equipment manufacturer, and that evacuation step is also the final check that no moisture has been left inside the tube.
Applications and Inspection Points
Split and packaged air conditioners: interconnecting line sets between indoor and outdoor units.
Refrigerant distribution pipework in chillers, rooftop units and multi-split systems.
Heat pumps for domestic and commercial heating, including CO₂ and propane systems with appropriate wall thickness.
Refrigeration plant: suction, discharge and liquid lines in cold stores, display cabinets and process refrigeration.
Transport refrigeration and vehicle air-conditioning circuits, where coiled tube is preferred for compact routing.
Incoming inspection should cover the mill certificate, the analysis for copper and phosphorus, eddy-current or pressure test reports, dimensional and wall-thickness verification, and the condition of the cap and the internal surface on a cut sample. The practical site checks that matter are that the caps stay in place until the moment of installation, that no tube is stored where it can pick up moisture or grit, and that open ends are re-capped at every break in the work. Tube that has been left open in a damp environment should be cleaned and purged, or discarded, rather than charged into a sealed circuit.
FAQ
Q: Which standard covers TP2 C12200 refrigerant tube?
ASTM B280 in the American system, GB/T 17791 in China and EN 12735-1 and EN 12735-2 in Europe. All three build the specification on phosphorus-deoxidised copper with strict internal cleanliness requirements.
Q: Why must refrigerant tube be deoxidised copper?
Because refrigerant lines are brazed. Tough-pitch copper contains oxide particles that react with hydrogen in a flame to form steam and crack the tube. Deoxidised TP2 C12200 cannot suffer that failure.
Q: What is the maximum wall thickness needed for R410A?
Wall thickness is chosen from the pressure rating required by the system design at the specified diameter. Standard ACR wall thickness satisfies ordinary R410A duties; higher-pressure systems such as transcritical CO₂ use heavier walls.
Q: How clean must the inside of the tube be?
Clean enough to meet the residue limit of the product standard. Tube is supplied degreased, purged, dried and capped, and the caps must stay in place until installation to keep that condition.
Q: Should nitrogen be used when brazing refrigerant lines?
Yes. A slow nitrogen purge through the tube displaces air and prevents oxide scale from forming on the hot internal surface while the joint is made.
Q: Can refrigerant tube be bent on site?
Soft annealed tube can be bent with a hand or powered bender to about one and a half to two times the outside diameter as a minimum centre-line radius, provided the correct bending shoe and mandrel are used.