Construction of CCS Flat Bar
The copper layer is applied over the steel core by electroplating or by continuous bonding processes. Typical copper layer thicknesses range from about 0.25 mm upward, and the copper content is commonly specified between 15% and 40% of the total mass, depending on the project specification. The bond between copper and steel is continuous, so the conductor can be cut, drilled and formed without the copper layer peeling.
Typical Sizes
CCS flat bar is commonly produced in rectangular sections such as 25 × 4 mm, 30 × 3 mm, 40 × 4 mm, 50 × 5 mm and larger sections up to 100 × 8 mm or more, in standard lengths of 6 m (or per project requirement). The required cross-section is determined by the earthing design (fault current, duration and permissible temperature rise), not by the conductor cross-section alone.
Key Advantages over Solid Copper Earth Bar
- High conductivity: the copper cladding carries the fault current with conductivity approaching that of solid copper.
- High mechanical strength: the steel core provides tensile strength significantly higher than annealed copper, reducing sag and damage during installation.
- Corrosion resistance: the continuous copper layer protects the steel core in soil and atmospheric exposure.
- Cost efficiency: less copper per meter than a solid copper bar of equal section.
- Lower scrap value: reduces the risk of theft, which is a practical concern for exposed earthing conductors.
Design References for Earthing Conductors
Earthing conductor sizing and layout are normally designed with reference to IEEE Std 80 (AC substation grounding) and IEC 62305-3 (lightning protection), together with applicable national electrical codes. The CCS flat bar itself is supplied to the mechanical and electrical requirements agreed in the project specification; confirm the copper thickness, conductivity and test requirements with the supplier.
Installation Guidance
- Joints and connections should be made by exothermic welding or compression connectors rated for CCS conductors, and the joint area must be cleaned before welding.
- Connections to steel structures or concrete reinforcement should be protected against galvanic corrosion.
- In soil, lay the flat bar on its flat face to maximize contact area, and backfill with low-resistivity soil where specified.
- After installation, measure the earth resistance and verify it meets the design requirement.
FAQ
What is the difference between CCS flat bar and solid copper earth bar?
CCS has a steel core with a copper cladding: it is stronger, lighter in copper content and cheaper than solid copper, with slightly lower conductivity per unit section; solid copper offers maximum conductivity at higher cost.
How do I choose the copper layer thickness?
The copper layer thickness is selected from the project specification: thicker layers (for example 0.5 mm or more) are specified for aggressive soil conditions and longer design life; thinner layers reduce cost where conditions are mild.
Can CCS flat bar be welded?
Yes. Joints are normally made by exothermic welding or brazing on the copper surface; mechanical clamps and compression lugs are also available for connections.
Is CCS suitable for lightning protection?
Yes. CCS conductors are widely used in lightning-protection down conductors and earthing systems designed to IEC 62305-3, combining adequate conductivity with the mechanical strength required for exposed installation.